VEX200 Measurement setup, capacity measurement

Calculation example, VEX200

Measurement set-up

 


Calculation example

Desired external output  

qV = 900 l/s (3240 m3/h)

pt = 250 Pa 

Selected solution

VEX250 with F7 filters
External pressure output pt = 250 Pa

Pressure drop supplement: F7 filters, pt = 45 Pa

Total pressure output, pt = 295 Pa

Reading specific power consumption, SFP = 2,300 J/m3

Absorbed power P1 =2300 x 900 x 10-3 = 2070 Watt


Diagram

Thik line Capacity curve with M5 filters
Doddet line SFP curve (J/m3)
Thin line Operating curves

A: Pressure drop supplement with F7 filters
B: Pressure drop with HCW/HCE

 

 

 

 

 

Calculation programs

Use EXHAUSTO's free calculation programs for calculating ventilation plant and system solutions

Go to Calculation Programs
Vex overview

VEX Summary

Get a quick overview of our entire range of compact VEX air handling units with heat recovery.

View the VEX summary here