EXHAUSTOInstituteData assumptionsVEXVEX, capacity measurementsVEX200, calculation example VEX200 Measurement setup, capacity measurementCalculation example, VEX200 Measurement set-up Calculation example Desired external output qV = 900 l/s (3240 m3/h) pt = 250 Pa Selected solution VEX250 with F7 filters External pressure output pt = 250 Pa Pressure drop supplement: F7 filters, pt = 45 Pa Total pressure output, pt = 295 Pa Reading specific power consumption, SFP = 2,300 J/m3 Absorbed power P1 =2300 x 900 x 10-3 = 2070 Watt Diagram Capacity curve with M5 filters SFP curve (J/m3) Operating curves A: Pressure drop supplement with F7 filters B: Pressure drop with HCW/HCE
Calculation programs Use EXHAUSTO's free calculation programs for calculating ventilation plant and system solutions Go to Calculation Programs
VEX Summary Get a quick overview of our entire range of compact VEX air handling units with heat recovery. View the VEX summary here