VEX170H

Technical data

VEX170

Unit data
Absorbed power 9,2 kW
Power supply 3 x 400 V + N + PE~ 50 Hz
Max. phase current 17.5 A *
Max. neutral current 24.0 A
Weight
Operation-ready unit
- with cross-flow heat exchanger type A
- with  standard cross-flow heat exchanger 

665 kg
626 kg
For transport into the location 411 kg **
Motor and motor control (MC) data
Motor type EC motor
Motor class in accordance with IEC TS 60034-30-2 IE5 (Ultra Premium Efficiency)
Voltage input 3 x 400 V
Current overload protection Built-in
Regulation Variable via motor control (MC)
Control signal  With integrated control system:
Modbus
For third-party control system:
0-10 V DC
* (power consumption is taken from two phases and is not sinusoidal)
** (excl. doors, heat exchanger and fan units)
 
Heating coils
Electric heating coil (HCE) 31.2 kW
Absorbed power total 40.4 kW
Power supply 3 x 400 V + N + PE~ 50 Hz
Max. phase current 62.5 A
Electric heating coil (HCE) 46.8 kW
Absorbed power total 56.0 kW
Power supply 3 x 400 V + N + PE~ 50 Hz
Max. phase current 85.0 A
Water heating coil (HCW)

Test pressure
3000 kPa
Max. operating pressure
1000 kPa
Number of rows of pipes
Qty. 2
Number of circuits
Qty. 11
Face area (H x W)
550 x 1042 mm
Pipe connection
DN25 (1")
Fin spacing
2 mm
Weight (without fluid)
16,3 kg
Water content
4,6 l

 

Fan data  
Max. total efficiency (A-D) 60,4%
ECO measurement set-up (A-D) A
Efficiency level requirements 62N (2015)
ECO efficiency level during optimal operating point 66.6N

Motor data (optimal operating point)
EC motor With motor controller
Absorbed power 4.62 kW
Airflow 7186 m3/h
Total pressure 1398 Pa
RPM during optimal operating point  2913

Conditions:
- Density = 1.2 kg/m3
- Pressure ratio < 1.11
- other points in acc. with EC327/2011 (see product instructions)

Temperature efficiency

Temperature efficiency, VEX170 with crossflow heat exchanger

Temperature efficiency, VEX170
stiplet streg
Efficiency with condensation:
Extract air = 20°C/55 RH
Outdoor air  = -10°C/50 RH
Balance between supply air/extract air = 1,0
kort-lang-stiplet-streg
Efficiency without condensation with imbalance:
Extract air = 25°C/28 RH
Outdoor air = 5°C/50 RH
Balance between supply air/extract air  = 0,8
fed streg Efficiency without condensation in acc. with EN308:
Extract air = 25°C/28 RH
Outdoor air = 5°C/50 RH
Balance between supply air/extract air = 1,0

Calculation

The temperature efficiency of the VEX air handling units are shown at different airflow ratios, calculated as:


t2,1 = Temperature of outdoor air (fresh air)
t2,2 = Temperature of supply air
t1,1 = Temperature of extract air

Extract air = 25 ºC / 30 % RH
Outdoor air (fresh air) = 5 ºC / 50 % RH
Temperature efficiency is stated in accordance with EN308 for dry heat recovery and is increased by condensation.
Sound data

VEX170

 

VEX170 LWA1-Extract side

 5406564_VEX170EX2

 

VEX170 LWA2 -Pressure side

 

5406565_VEX170EX2

 

Suction side (outdoor air/extract air):
LW1 = LWA1 + Kw
LWA1 to be read off

Pressure side (supply air/exhaust air):
LW2 = LWA2 + KW
LW2 to be read off

Surroundings:
LW3 = LWA1 + KW
LWA1 to be read off
LpA3 = LWA1 + KpA

 

  KW(dB) KWA
dB(A)



 KpA
dB (A)

Hz I-III 63 125 250 500 1K 2K 4K 8K
LWA1 I 8 -1 -4 0 -3 -15 -23 -32
II 8 -2 2 -3 -5 -16 -26 -35
  III 8 8 3 -3  -6 -18  -30 -31
LW2 I -9 -11 -11 -4 -3 -8 -14 -19
II -8 -12 -0 -4 -4 -9 -15 -22
  III -7 -5 -3 -2  -3 -10 -19  -17
LW3 I 11 3 -8 -10 -15 -23 -30 -35 -8 -25
II 11 2 -5 -14 -17 -24 -30 -31 -8 -26
  III 11 8 -3 -11 -16 -22  -22 -19 -4 -21

 

Measurement arrangements

 

5409217_VEX140_sound_data

 

5409214_VEX140_sound_data

To calculate sound data please see our product selection tool.


Dimensioned drawings

VEX170

 

VEX170 - Horizontal, Left (unit dimensions in mm)

 

RD11370_VEX170HL_HCW

 

 desired spigot location, position A or B, to be specified in order.
*) Allow a height for service in front of the unit equivalent to the unit width.
**) Allow a min. of 300 mm free height for service.

VEX170 - Horizontal, Right (unit dimensions in mm)

 

RD11397_VEX170HR_HCW

1.1 Extract air 1.2 Exhaust air 2.1 Outdoor air 2.2 Supply air

 desired spigot location, position A or B, to be specified in order.
*) Allow a height for service in front of the unit equivalent to the unit width.
**) Allow a min. of 300 mm free height for service.

Cooling and heating coils

The following cooling and heating coils are suitable for VEX170/VEX170CF

Type Model
CW cooling coil (water)  CW050x060I
CW076x125U
DX cooling/heating coil DX050x060

Add all about the product series VEX170H

CONTACT US TODAY

Get free advice on ventilation products and system solutions


Export Requests:
EXHAUSTO Export
Odensevej 76
DK 5550 Langeskov

Tel +45 6566 1236
E-mail: export@exhausto.dk

Calculation programs

Use EXHAUSTO's free calculation programs for calculating ventilation plant and system solutions

Go to Calculation Programs
Vex overview

VEX Summary

Get a quick overview of our entire range of compact VEX air handling units with heat recovery.

View the VEX summary here