DEX3120

Technical Data

DEX3120 - Decentralised Ventilation

Technical Data 


Airflow in acc. ErP2018 (ECO-design)

1.400 m³/h
Minimum Airflow  300 m³/h
Height  600 mm
Width 
2.404 mm
Depth 
1.403 mm
Size  2,02 m²
Fan/Motor EC-Motor
Heat Exchanger Technology

Counterflow 

Efficiency  (SFP, EN308)  ∼ 82% (@1.200 m³/h)
Weight  250 kg
Filters, Supply Air  Standard: ePM1 55% (F7)
Filters, Exhaust Air Standard:  ePM10 60% (M5)
Filter Options

Prefilter ISO Coarse 85% (G4), ePM10 60% (M5)
ePM1 55% (F7), ePM1 80% (F9)

Casing Classification (ISO12944 Corrosion)
Corrosion class C4
Control System Integrated EXcon-Automatik

 

Elektrical Data:

Size Heating-/cooling coil Power supply Absorbed power Max. phase current
DEX3060 None 1x230V+N+PE ~ 50Hz 0,7 kW 3,0 A
DEX3060 Water heating coil 1x230V+N+PE ~ 50Hz
0,7 kW 3,0 A
DEX3060 Electric heating coil
1,5 kW
1x230V+N+PE ~ 50Hz
2.2 kW 9,6 A
DEX3060 Elvarmeflade
4,5 kW
3x400V+N+PE ~ 50Hz
5.4 kW 7,8 A
DEX3090 None 1x230V+N+PE ~ 50Hz 0,7 kW 3,0 A
DEX3090 Water heating coil
1x230V+N+PE ~ 50Hz
0,7 kW 3,0 A
DEX3090 Electric heating coil
2,5 kW
1x230V+N+PE ~ 50Hz
3,2 kW 13,7 A
DEX3090 Electric heating coil
6,0 kW
3x400V+N+PE ~ 50Hz
6,9 kW 10,0 A
DEX3120 None 1x230V+N+PE ~ 50Hz 1,1 kW 5,0 A
DEX3120 Water heating coil
1x230V+N+PE ~ 50Hz
1,1 kW 5,0 A
DEX3120 Electric heating coil
3,0 kW
3x400V+N+PE ~ 50Hz
4,4 kW 6,4 A
DEX3120 Electric heating coil
9,0 kW
3x400V+N+PE ~ 50Hz
10,4 kW 15,2 A
Temperature efficiency

Temperature efficiency, DEX3120

The temperature efficiency and, to a lesser extent, the SFP/SEL values for a specific air handling unit are closely connected to the heat exchanger itself and depend upon the manufacturer. As suppliers can change from time to time, small changes in the technical data can occur, which is why it is always recommended that you perform a calculation for the particular project using our calculation software, EXselectPRO.

 Temperature-efficiency-curve-for-DEX3120
The curve is intended as a guideline, and it is recommended that a calculation be performed using the calculation software EXselectPRO for the individual project.

fed streg Efficiency without condensation in acc. with EN308:
Extract air = 25°C/28 RH
Outdoor air = 5°C/50 RH
Balance between supply air/extract air = 1,0

Calculation

 The temperature efficiency of the VEX units is shown at different airflow ratios, calculated as:

 

t2,1
t2,2
t1,1
=
=
=
Temperature of outdoor air (fresh air)
Temperature of supply air
Temperature of extract air
Temperature efficiency is stated in accordance with EN308 for dry heat recovery and is increased by condensation.
Dimensional Drawings

DEX3120 - Dimensional Drawings

Dimensional drawing, DEX3120 standard version

Dimensional drawing, DEX3120 standard version 

Dimensional drawing, DEX3120 semi-integrated version

Dimensional drawing, DEX3060 semi-integrated version

Add all about the product series DEX3120

CONTACT US TODAY

Get free advice on ventilation products and system solutions


Export Requests:
EXHAUSTO Export
Odensevej 76
DK 5550 Langeskov

Tel +45 6566 1236
E-mail: export@exhausto.dk

Calculation programs

Use EXHAUSTO's free calculation programs for calculating ventilation plant and system solutions

Go to Calculation Programs