BESF146 box fan

Technical data

Technical data, BESF146 

MODEL BESF146-4-1
Motor  

Motor 

Single-phase motor
Nominal rpm (N)  1400 rpm at 50 Hz
Electric supply (U)  1x230 V
Overload protection      Integral thermal cutout (TP211) in motor power circuit

Max absorbed current* (I)

 0.35 A.
Max. absorbed power (P1)**  0.10 kW
Motor output (P2)**  0.04 kW

Supply
 
Supply (power cable) 3 x 0.75 mm2
Length 1.4 m
Other data  
Weight  13 kg.

Conditions:

  • * I is the maximum absorbed current throughout the control range - or the full load current if this is larger
  • ** P1 is the maximum absorbed power from the mains supply, where P2 is the motor's nominal output.
  • Stated data are for t = 20°C
  • Density = 1.2 kg/m3
  • Gas temperature: min. -12°C, max. +60° C
  • Ambient temperature: Max. +40° C
  • Pressure ratio: < 1,11
Capacity diagram

BESF146-4-1

 

BESF146-4-1 kapacitetskurve

Sound data

Sound data, BESF146

 

BESF146 lydkurve

 

   
 Kw[dB]
 K[dB(A)]
  I-IV 63 125 250 500 1 k 2 k 4 k 8 k KWA KpA
Lw1 I 5 7 1 -3 --3 -12 -16 -23    
II 11 10 2 -3 -5 -14 -20 -31    
III 5 6 0 0 -6 -14 -20 -30  
IV 10 9 0 0 -8 -17 -24 -36    
Lw2 I 6 7 3 0 1 -9 -14 -20 4  
II 12 11 3 -2 -5 -13 -19 -30 1  
III 8 7 3 1 -1 -11 -15 -22 3  
IV 13 10 2 -2 -7 -16 -23 -35 0  
Lw3 I -4 -10 -15 -5 -22 -25 -23 -29 -8 -21
II -4 -10 -15 -5 -22 -25 -23 -29 -8 -21
III -4 -10 -15 -5 -22 -25 -23 -29 -8 -21
IV -4 -10 -15 -5 -22 -25 -23 -29 -8 -21
Dimensional drawing

BESF146

 

BESF146 målskitse

Add all about the product series BESF146 box fan

CONTACT US TODAY

Get free advice on ventilation products and system solutions


Export Requests:
EXHAUSTO Export
Odensevej 76
DK 5550 Langeskov

Tel +45 6566 1236
E-mail: export@exhausto.dk

Calculation programs

Use EXHAUSTO's free calculation programs for calculating ventilation plant and system solutions

Go to Calculation Programs
Vex overview

VEX Summary

Get a quick overview of our entire range of compact VEX air handling units with heat recovery.

View the VEX summary here