BESF280 box fan

Technical data

Technical data, BESF280-4-3EC

MODEL    BESF280-4-3EC OGSR
Fan data
Max. overall efficiency 58,5 %
ECO measurement set-up (A-D)  D
Efficiency requirements  49, N(2015)
ECO efficiency at optimal operating point 68,9

Motor

Motor 

EC motor with integral VSD
Optimal operating point:
Absorbed power
Airflow
Total pressure
Rpm

 
493 W
1870 m3/h
555 Pa
1306 rpm

Nominal rpm (N) 1448 rpm 
Electric supply (U)   3 x 230D/400Y
Overload protection     Integrated in motor control

Max absorbed current* (I)

5.3 A
Max. absorbed power (P1)** 3.2 kW
Motor output (P2)** 2.2 kW

Other data
Weight 65 kg 

 

 

Conditions:

  • * I is the maximum absorbed current throughout the control range - or the full load current if this is larger
  • ** P1 is the maximum absorbed power from the mains supply, where P2 is the motor's nominal output.
  • Stated data for for t = 20°C
  • Density = 1.2 /m3
  • Values are based on the use of a transition piece equivalent to OGSR
  • Gas temperature: min. -12°C, max. +60° C
  • Ambient temperature: Max. +40°C
  • Pressure ratio: < 1,11
  • other points in acc. with EC327/2011 - see product instructions
Capacity diagram

Capacity diagram, BESF280-4-3EC

BESF280-4-3EC kapacitetskurve

Sound data

Sound data, BESF280

 

 


Kw[dB]
K[dB(A)]
I-IV 63 125 250 500 1 k 2 k 4 k 8 k KWA KpA
Lw1 I 3 5 -1 -7 -6 -7 -9 -11
II 14 11 2 -8 -8 -11 -13 -16
III 6 7 0 -7 -5 -8 -11 -13
IV 16 11 2 -7 -7 -11 -14 -20
Lw2 I 5 7 3 -2 -2 -4 -9 -13 3
II 12 12 6 -3 -3 -7 -11 -16 3
III 9 8 4 -1 -1 -4 -9 -13 4
IV 17 13 7 0 -2 -6 -10 -16 5
Lw3 I -16 -19 -21 -21 -26 -32 -35 -15 -16 -30
II -12 -16 -18 -21 -21 -28 -31 -8 -10 -24
III -14 -19 -20 -17 -24 -32 -33 -7 -9 -23
IV -9 -17 -20 -8 -24 -27 -27 -2 -3 -17
Dimensional drawing

BESF280

 

BESF280

 

BESF280 målskitse

 

BESF280-EC

 

BESF280EC målskitse

Add all about the product series BESF280 box fan

CONTACT US TODAY

Get free advice on ventilation products and system solutions


Export Requests:
EXHAUSTO Export
Odensevej 76
DK 5550 Langeskov

Tel +45 6566 1236
E-mail: export@exhausto.dk

Calculation programs

Use EXHAUSTO's free calculation programs for calculating ventilation plant and system solutions

Go to Calculation Programs
Vex overview

VEX Summary

Get a quick overview of our entire range of compact VEX air handling units with heat recovery.

View the VEX summary here