DTH 160 roof fan, horizontal exhaust

Technical data

DTH160

MODEL    DTH160-4-1
Motor

Motor 

Single-phase motor
Nominal rpm (N)  1400 rpm at 50 Hz
Electric supply (U)  1x230 V
Overload protection      Integral thermal cutout (TP211) in motor power circuit

Max absorbed current* (I)

 0.14 A.
Max. absorbed power (P1)**  0.04 kW
Motor output (P2)**  0.01 kW

Supply
Supply (power cable) 3 x 0.75  mm2
Length 0.8 m

Other data
Weight 9 kg

 

Conditions:

  • * I is the maximum absorbed current throughout the control range - or the full load current if this is larger
  • ** P1 is the maximum absorbed power from the mains supply, where P2 is the motor's nominal output.
  • Stated data are for t = 20°C
  • Density = 1.2 kg/m3
  • Gas temperature: min. -12°C, max. +60° C
  • Ambient temperature: Max. +40°C 
  • Pressure ratio: < 1,11
Capacity diagram

DTH160-4-1

 

DTH160-4-1 kapacitetskurve
Dimensional drawing

DTH160

DTH160 målskitse
Sound data

DTH160

 

DTH160 lydkurve

 

  K[dB(A)]   Kw[dB]
  KwA KpA 125 250  500 1 k 2 k  4 k  8 k 
      I II I II  Hz Hz  Hz Hz Hz 
Lw1  0   5 10 4 -1 -1 -8 -22 -28 -36
Lw3 4 -7 -4 -4 -2 -2 1 -19 -19 -26
LpA3   -25                  

Add all about the product series DTH 160 roof fan, horizontal exhaust

CONTACT US TODAY

Get free advice on ventilation products and system solutions


Export Requests:
EXHAUSTO Export
Odensevej 76
DK 5550 Langeskov

Tel +45 6566 1236
E-mail: export@exhausto.dk

Calculation programs

Use EXHAUSTO's free calculation programs for calculating ventilation plant and system solutions

Go to Calculation Programs
Vex overview

VEX Summary

Get a quick overview of our entire range of compact VEX air handling units with heat recovery.

View the VEX summary here