VVR315
The motor controller for the EC motor is provided in a box which can either hang on the wall outside or be retracted within the duct.
NB:
|
Due to EMC requirements the cable between the EC control and the EC motor must not be elongated.
|
Fan data |
Max. overall efficiency |
55,1 % |
ECO measurement set-up (A-D) |
C |
Efficiency requirements |
62, N(2015) |
ECO efficiency at optimal operating point |
76,2 |
Motor |
Motor
|
EC motor with integral VSD |
Optimal operating point:
Absorbed power
Airflow
Total pressure
Rpm |
299 W
2129 m3/h
279 Pa
1446 rpm
|
Nominal rpm (N) |
1635 rpm |
Electric supply (U) |
1 x 230 V ~ 50 Hz |
Overload protection |
Integrated in motor control |
Max absorbed current* (I) |
2,6 A |
Max. absorbed power (P1)** |
0.43 kW |
Motor output (P2)** |
0,37 kW |
Supply |
Supply (power cable) |
- |
Length |
- |
Other data |
Weight |
29 kg |
Conditions:
- * I is the maximum absorbed current throughout the control range - or the full load current if this is larger
- ** P1 is the maximum absorbed power from the mains supply, where P2 is the motor's nominal output.
- Stated data are for t = 20°C
- Density = 1.2 kg/m3
- Gas temperature: min. -12°C, max. +60° C
- Ambient temperature: Max. +40° C
- Pressure ratio: < 1,11
- other points in acc. with EC327/2011 - see product instructions