- EXHAUSTO.com
- Products
- Air handling units
New compact series with rotary heat exchanger in horizontal design - 11 sizes, up to 9340 m³/h and a comprehensive accessories program

Multi-occupancy residential housing
New
Refurbishment
Non-residential buildings
Schools
VEX1000 brings fresh, filtered air into the building and recovers heat from the exhaust air using the high-efficiency heat exchanger. The incoming air can be heated and/or cooled using a complete range of integrated cooling and heating coils.
VEX1000 is a compact unit designed to deliver the highest possible air capacity with the least possible space requirement.
VEX1000RS can be equipped with automatic leakage control, ALC™, which eliminates the transfer of particles, aerosols, viruses, etc., from exhaust air to supply air through the heat exchanger. Thus, you get all the benefits of a rotary heat exchanger without leakage:
Moisture transfer provides improved indoor climate and higher productivity
Does not require defrosting
Saves energy by cooling recovery
No need to handle condensation
Compact design
1x230V or 3x400V power supply
Mixing section (VEX1030 – 1080)
Duct silencers
Outdoor units (Roof, plinth, doorstop, damper motor cover, electric heater for control box)
Shut-off damper
Integrated coils (Water, Electric, DX)
External casing for DX and combined water heating and cooling coil with drip tray and droplet separator
Patented automatic leakage control (ALC™)
Rotating heat exchanger with sorption and epoxy coating
Choice between bag and panel filter
Choice between integrated EXcon+ control, controller ready or without control
Flexible duct connections
Option for extract and/or exhaust air outlet positioned on top
Class 3 damper


| Variants | A (mm) | D (mm) | Ø (mm) | E (mm) | F (mm) | I (mm) | J (mm) | K (mm) | L (mm) | M (mm) | P (mm) | Weight (kg) | N (mm) | O (mm) | B (mm) | C (mm) | G (mm) | H (mm) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| VEX1005RS | 1307 mm | 855 mm | 250 mm | 720 mm | 683 mm | 234 mm | 617 mm | 360 mm | 310 mm | 232 mm | 258 mm | 172 kg | ||||||
| VEX1010RS | 1347 mm | 1135 mm | 315 mm | 720 mm | 683 mm | 274 mm | 794 mm | 355 mm | 305 mm | 224 mm | 264 mm | 207 kg | 450 mm | 250 mm | ||||
| VEX1015RS | 1461 mm | 1135 mm | 400 mm | 809 mm | 772 mm | 306 mm | 825 mm | 400 mm | 350 mm | 245 mm | 296 mm | 238 kg | 500 mm | 250 mm | ||||
| VEX1020RS | 1461 mm | 1135 mm | 400 mm | 905 mm | 868 mm | 311 mm | 825 mm | 450 mm | 400 mm | 245 mm | 311 mm | 255 kg | 600 mm | 250 mm | ||||
| VEX1030RS | 1660 mm | 1339 mm | 1016 mm | 970 mm | 980 mm | 355 mm | 500 mm | 204 mm | 359 mm | 349 kg | 800 mm | 250 mm | 830 mm | 830 mm | 500 mm | 400 mm | ||
| VEX1035RS | 1660 mm | 1339 mm | 1117 mm | 1071 mm | 980 mm | 355 mm | 550 mm | 204 mm | 359 mm | 381 kg | 800 mm | 250 mm | 830 mm | 830 mm | 500 mm | 400 mm | ||
| VEX1045RS | 1730 mm | 1524 mm | 1217 mm | 1172 mm | 1125 mm | 400 mm | 600 mm | 219 mm | 360 mm | 450 kg | 1000 mm | 250 mm | 865 mm | 865 mm | 700 mm | 500 mm | ||
| VEX1050RS | 1730 mm | 1524 mm | 1319 mm | 1274 mm | 1120 mm | 400 mm | 650 mm | 230 mm | 359 mm | 481 kg | 1000 mm | 250 mm | 865 mm | 865 mm | 700 mm | 500 mm | ||
| VEX1060RS | 1800 mm | 1734 mm | 1403 mm | 1357 mm | 1280 mm | 450 mm | 700 mm | 269 mm | 359 mm | 548 kg | 1000 mm | 250 mm | 900 mm | 900 mm | 900 mm | 500 mm | ||
| VEX1065RS | 1800 mm | 1734 mm | 1493 mm | 1460 mm | 1280 mm | 450 mm | 750 mm | 252 mm | 360 mm | 597 kg | 1000 mm | 250 mm | 900 mm | 900 mm | 900 mm | 500 mm | ||
| VEX1080RS | 2104 mm | 1906 mm | 1609 mm | 1561 mm | 1410 mm | 485 mm | 795 mm | 282 mm | 452 mm | 741 kg | 1000 mm | 400 mm | 1052 mm | 1052 mm | 1000 mm | 700 mm |
| Variants | Max. airflow ErP (m³/h) | Minimum airflow |
|---|---|---|
| VEX1005RS | 900 m³/h | 110 |
| VEX1010RS | 1280 m³/h | 130 |
| VEX1015RS | 1760 m³/h | 230 |
| VEX1020RS | 2360 m³/h | 240 |
| VEX1030RS | 3100 m³/h | 400 |
| VEX1035RS | 3950 m³/h | 420 |
| VEX1045RS | 4860 m³/h | 610 |
| VEX1050RS | 5770 m³/h | 630 |
| VEX1060RS | 6260 m³/h | 630 |
| VEX1065RS | 7500 m³/h | 650 |
| VEX1080RS | 9340 m³/h | 1030 |
| Variants | Frequency (Hz) | Max. electrical output of unit (kW) | Voltage (V) | Maximum current - unit (A) |
|---|---|---|---|---|
| VEX1005RS | 50 Hz | 1,4 kW | 1x230 V | 5,7 A |
| VEX1010RS | 50 Hz | 1,4 kW | 1x230 V | 5,7 A |
| VEX1015RS | 50 Hz | 2,6 kW | 1x230 V | 10,9 A |
| VEX1020RS | 50 Hz | 2,6 kW | 1x230 V | 10,9 A |
| VEX1030RS | 50 Hz | 4 kW | 3x400 V | 7,4 A |
| VEX1035RS | 50 Hz | 4 kW | 3x400 V | 7,4 A |
| VEX1045RS | 50 Hz | 5,6 kW | 3x400 V | 10 A |
| VEX1050RS | 50 Hz | 5,6 kW | 3x400 V | 10 A |
| VEX1060RS | 50 Hz | 5,4 kW | 3x400 V | 10 A |
| VEX1065RS | 50 Hz | 5,4 kW | 3x400 V | 10 A |
| VEX1080RS | 50 Hz | 7,6 kW | 3x400 V | 13,2 A |

VEX1000 leveres færdigtestet i enten 1 eller 2 moduler fra fabrikken.
VEX1005 til VEX 1020 leveres som et samlet modul, mens VEX1030 til VEX1080 leveres i to moduler.
Dette gør at VEX1000 nemt kan transporteres til montagestedet.

MECHANICAL PERFORMANCE: In accordance with DS/EN 1886 and certified by Eurovent
Strength of unit casing: D2 (M)
Leakage at negative pressure of -400 Pa: L1 (M)
Leakage at positive pressure of +700 Pa: L2 (M)
Filter bypass leakage: F9 at negative and positive pressure
Thermal transmittance: T2 (M)
Thermal bridging factor: TB2

VEX1000 is delivered fully tested in either 1 or 2 modules from the factory.
VEX1005 to VEX 1020 are delivered as a complete module, while VEX1030 to VEX1080 are delivered in two modules.
The product can be delivered on adjustable mouting feets or mounted together on a baseframe.
A quickguide is included, which instructs in easy and quick assembly of the product. Detailed instructions as well as service guides are easily accessed via the QR code on the front of the unit.

For projects with extra limited access conditions, VEX1000 can be delivered as SPLIT, where the unit can be easily and quickly disassembled, transported into the building, and reassembled.

Flexible placement of control box
Control and electrical panel are included in a separate control box, which can be mounted beside the unit or on the wall, up to 10 m from the VEX-unit. In this way, the box can be placed where it is most appropriate in terms of service and maintenance.

VEX1000RS is available with the option for extract and/or exhaust air nozzle placed at the top of the unit to provide greater flexibility at the installation site.
For units with round side nozzles and rectangular top nozzles, transition piece from square to round are offered.
NOTE. VEX1000 with rotary heat exchanger is also available with 4 top nozzles. See under the product VEX1000RT.

VEX1000 can be delivered with 3 control options:
Integrated EXcon+ control (Standard) – The unit is equipped with EXcon+. All internal electrical and control components in the unit are connected to the included control box and tested from the factory.
Controller Ready (Option) – All internal electrical and control components in the unit are connected to the electrical and control box, which is prepared for the installation of alternative control chosen by the customer. (External control components are not included)
Without control (Option) – The unit is delivered without a control box, control, electrical wiring, and sensors. The customer is responsible for their own electrical and control setup. (Controls and motors for rotating heat exchanger, fans, and dampers are included)
The new EXcon+ control ensures optimal indoor climate management in virtually all application areas.
The intuitive user interface adapted to predefined user groups and optimized calendar function ensures easy and quick setting and adjustment of the indoor climate.
EXcon+ control is used to manage, among other things, air flow, heating, and cooling. How and when control switches between built-in functions are set in the operating program. The program can, if necessary, be overridden by temporary manual control, after which it returns to the active operating program.
Choosing EXcon+ provides, in addition to a wide range of standard control modes, the opportunity to use EXHAUSTO's patented Automatic Leakage Control (ALC™) and Dynamic Pressure Control (aDCV).
Automatic Leakage Control (ALC™) allows taking advantage of a rotary heat exchanger without transferring contaminated air via the heat exchanger.
Dynamic Pressure Control (aDCV) enables optimized operation with constant pressure regulation of ventilation systems with variable air volumes. Through the patented adaptive pressure regulation, up to 20% energy savings can be achieved compared to a demand-controlled system with constant pressure regulation (DCV).
EXcon+ control can be operated from a control panel, BMS, or web server over a network or via integrated WiFi. WiFi can be easily accessed from your tablet or PC by following the quick guide that comes with the control box.
EXcon+ network communication supports BacNet over TCP/IP and MODBUS over RS485 or TCP/IP.