VEX360H

Technical data

Technical data, VEX360H

Unit data:
Min. airflow 1 100 m³/h
Max. airflow 5,360 m³/h
Power consumption 5.0 kW
Power supply 3 x 400 V + N + PE∼50 Hz
Max. phase current 18.0 A (Power consumption is taken from two phases and is not sinusoidal).
Max. neutral current 23.5 A (Dimensioned current)
 
Operational-ready unit weight 702 kg
Weight for internal transport 310 kg heat exchanger section
156 kg fan section (qty. 2)
 80 kg base

Ambient temperature (operating)

At temperatures below -25˚C (with outdoor installation), use of a thermostatically controlled heater in automated control box is recommended.

-30°C to +50°C 
 
Motor and motor control (MC) data
Motor type EC motor
Motor class
in accordance with IEC TS 60034-30-2
IE5 (Ultra Premium Efficiency)
Voltage input 1 x 230 V
Current overload protection Built-in
Regulation Variable via motor control (MC)
Control signal with control system Modbus
Control signal with third party control system 0–10 VDC
Fluid temperature (air) -40°C to +40°C

Fan data

 
Max. total efficiency (A-D) 57,1 %
ECO measurement set-up (A-D) A
Efficiency level requirements 62N (2015)
ECO efficiency level during optimal operating point 67.2N

 

Motor data (optimal operating point)

EC motor With motor controller
Power consumption 2.36 kW
Airflow 4551 m3/h
Total pressure 1065 Pa
RPM during optimal operating point  3078

 

 Conditions:

- Density = 1.2 kg/m3
- Pressure ratio < 1,11
- other points in acc. with EC327/2011 (see product instructions)

Temperature efficiency

Temperature efficiency, VEX360H

The temperature efficiency and, to a lesser extent, the SFP/SEL values for a specific air handling unit are closely connected to the heat exchanger itself and depend upon the manufacturer. As suppliers can change from time to time, small changes in the technical data can occur, which is why it is always recommended that you perform a calculation for the particular project using our calculation software, EXselectPRO.

VEX360 temperaturvirkningsgrad
The curve is intended as a guideline, and it is recommended that a calculation be performed using the calculation software EXselectPRO for the individual project.

stiplet streg
Efficiency with condensation:
Extract air = 20°C/55 RH
Outdoor air  = -10°C/50 RH
Balance between supply air/extract air = 1,0
kort-lang-stiplet-streg
Efficiency without condensation with imbalance:
Extract air = 25°C/28 RH
Outdoor air = 5°C/50 RH
Balance between supply air/extract air  = 0,8
fed streg Efficiency without condensation in acc. with EN308:
Extract air = 25°C/28 RH
Outdoor air = 5°C/50 RH
Balance between supply air/extract air = 1,0

 

 

Calculation

The temperature efficiency of the VEX units is shown at different airflow ratios, calculated as:



t2,1 = Temperature of outdoor air (fresh air)
t2,2 = Temperature of supply air
t1,1 = Temperature of extract air
Dimensional drawings

Dimensional drawings, VEX360H

VEX360H - Left

VEX360H målskitse left

1.1 Extract air 1.2 Exhaust air 2.1 Outdoor air 2.2 Supply air

 
All dimensions in mm.

1) Allow a distance for service in front of the unit that is equivalent to the unit depth
2) Allow min. 200 mm free height for service

The doors can be removed for internal transport, allowing the heat exchanger sections to be moved through a 900 x 2,000 mm opening.

 

 

VEX360H - Right

 

VEX360H målskitse right

1.1 Extract air 1.2 Exhaust air 2.1 Outdoor air 2.2 Supply air

All dimensions in mm.

1) Allow a distance for service in front of the unit that is equivalent to the unit depth
2) Allow min. 200 mm free height for service 

The doors can be removed for internal transport, allowing the heat exchanger sections to be moved through a 900 x 2,000 mm opening.

 

Outdoor model with cover

With outdoor installation, the unit must be secured to the building at the points shown in the instructions.

VEX360H split skitse

 

Condensation outlet

The condensation outlet (DN32) can be lead out in all four directions. EXHAUSTO offers a complete water trap and heating cables for the outlet as accessories.
(The condensation pipe is not supplied by EXHAUSTO).

 ==== Optional channels

SPLIT unit

SPLIT unit, VEX360H

If the VEX360 needs to be transported through passages that would otherwise be too small for it, if it can be ordered as a SPLIT model.

As a SPLIT model, the unit is delivered assembled but not sealed, so that it can be split into smaller sections on the site and transported in smaller sections to the location where it is to be installed.

This work must be carried out by a certified EXHAUSTO service technician.

VEX350360 Split

Cooling and heating coils

Cooling and heating coils, VEX350/360

The following cooling and heating coils are suitable for VEX350/360

Type Model
HE electric heating coil  HE05x08 - three sizes 9/12/15 kW
HW water heating coil HW050x080
HW070x080
CW cooling coil (water)  CW050x080I
CW065x100U
DX cooling/heating coil DX050x080

Add all about the product series VEX360H

CONTACT US TODAY

Get free advice on ventilation products and system solutions


Export Requests:
EXHAUSTO Export
Odensevej 76
DK 5550 Langeskov

Tel +45 6566 1236
E-mail: export@exhausto.dk

Calculation programs

Use EXHAUSTO's free calculation programs for calculating ventilation plant and system solutions

Go to Calculation Programs
Vex overview

VEX Summary

Get a quick overview of our entire range of compact VEX air handling units with heat recovery.

View the VEX summary here