VEX100 Air handling unit

VEX100

Air handling unit

Compact unit that can be put together to match the given requirements for process ventilation
VEX100
VEX100 range

VEX140, 150 and 160 can be ordered in either a Horizontal or Vertical version, whereas VEX170 can only be ordered in Horizontal.

This is a very flexible range of air handling units, which can be ordered as LEFT or RIGHT versions and with spigot locations in the side, top or bottom.

In principle, EXHAUSTO VEX units are designed for use in comfort ventilation - i.e. under ordinary operating conditions.
VEX100

Product advantages

  • Compact units
  • Built-in electric or water heating coil
  • Flexible spigot positions
  • Horizontal and vertical models
  • Can be ordered for outdoor installation

VEX100 brings fresh, filtered air into the building and recovers heat from the extract air by means of its highly efficient heating heat exchanger. The incoming air can be heated and/or cooled using a complete range of heating/cooling coils.

VEX100 is suitable for tasks not covered by the Ecodesign Directive and where there is no need for such a high efficiency rating. For instance, for ventilating kitchens, bakeries, etc., where there is typically a surplus of heat but also a requirement for pre-heated supply air to the location.

Motor class in accordance with IEC TS 60034-30-2 Current overload protection Conditions

IE5 (Ultra Premium Efficiency)

Built-in

Conditions:> Density = 1.2 kg/m3> Pressure ratio < 1.11 > Other points in acc. with EC327/2011 (see product instructions)

References Max. Total efficiency (A-D) (%) Efficiency level requirements ECO efficiency level during optimal operating point Overload protection
VEX140, horizontal version

58,1

62N (2015)

76,2N

Built-in

VEX150, horizontal version

60

62N (2015)

74,4N

Built-in

VEX160, horizontal version

57,1

62N (2015)

67,2N

Built-in

VEX170H

60,4

62N (2015)

66,6N

Built-in

VEX140, in vertical version

58,1

62N (2015)

76,2N

Built-in

VEX150, vertical version

60

62N (2015)

74,4N

Built-in

VEX160, vertical version

57,1

62N (2015)

67,2N

Built-in

Conditions:

  • Density = 1.2 kg/m3
  • Pressure ratio < 1.11
  • other points in acc. with EC327/2011 (see product instructions)

References Voltage input Regulation Control signal with control system Control signal with third party control system
VEX140, horizontal version

1 x 230 V

Variable via motor control (MC)

Modbus

0-10 V DC

VEX150, horizontal version

1 x 230 V

Variable via motor control (MC)

Modbus

0-10 V DC

VEX160, horizontal version

1 x 230 V

Variable via motor control (MC)

Modbus

0-10 V DC

VEX170H

3 x 400 V

Variable via motor control (MC)

Modbus

0-10 V DC

VEX140, in vertical version

1 x 230 V

Variable via motor control (MC)

Modbus

0-10 V DC

VEX150, vertical version

1 x 230 V

Variable via motor control (MC)

Modbus

0-10 V DC

VEX160, vertical version

1 x 230 V

Variable via motor control (MC)

Modbus

0-10 V DC

Dimensional drawings for VEX100H = horizontal version and VEX100V– vertical version respectively – both shown with round ducts.

VEX100 VEX100
References A (mm) B (mm) C (mm) Ø connection (fresh air or exhaust) (mm) Ø connection (discharge or air supply) (mm) Weight (kg) Weight for transport
VEX140, horizontal version

1365

1145

750

315

315

190

105 kg (excl. doors, heat exchanger and fan sections)

VEX150, horizontal version

1600

1295

835

400

400

278

164 kg (excl. doors, heat exchanger and fan sections)

VEX160, horizontal version

1820

1495

940

500

500

  • with cross-flow heat exchanger type A: 360 kg > with standard cross-flow heat exchanger: 355 kg

202 kg (excl. doors, heat exchanger and fan sections)

VEX170H

2200

1895

1240

   

"> with cross-flow heat exchanger type A: 665 kg > with standard cross-flow heat exchanger: 626 kg"

411 kg (excl. doors, heat exchanger and fan sections)

VEX140, in vertical version

1145

1365

750

315

315

190

105 kg (excl. doors, heat exchanger and fan sections)

VEX150, vertical version

1600

1295

 

400

400

278

164 kg (excl. doors, heat exchanger and fan sections)

VEX160, vertical version

1820

1495

940

500

500

  • with cross-flow heat exchanger type A: 360 kg > with standard cross-flow heat exchanger: 355 kg

202 kg (excl. doors, heat exchanger and fan sections)

References Minimum airflow Max. airflow (m³/h)
VEX140, horizontal version

250

1900

VEX150, horizontal version

500

3060

VEX160, horizontal version

600

4480

VEX170H

660

8170

VEX140, in vertical version

250

1900

VEX150, vertical version

500

3060

VEX160, vertical version

600

4480

References Frequency (Hz) Max. power of electrical coil 1 (kW) Max. electrical output of unit (kW) Voltage (V) Max. power of electrical coil 2 Maximum current - unit (A) Maximum current - first coil (A) Maximum current - second coil (A) Max current of zero (A)
VEX140, horizontal version

50

 

1,6

1x230

 

12,5

     
VEX150, horizontal version

50

12

2,7

3x400

18

8,7

26

34,7

15,0

VEX160, horizontal version

50

14,4

4,8

3x400

21,6

15,5

36,5

46,7

23,5

VEX170H

50

31,2

9,2

3x400

46,8

17,5

62,5

85

 
VEX140, in vertical version

50

 

1,6

1x230

 

12,5

     
VEX150, vertical version

50

12

2,7

3x400

18

8,7

26

34,7

15,0

VEX160, vertical version

50

14,4

4,8

3x400

21,6

15,5

36,5

46,7

23,5

MEKANISK YDEEVNE: In accordance with ds/en 1886 and certified by Eurovent

In accordance with ds/en 1886 and certified by Eurovent:

  • Strength of unit housing: D1 (M)
  • Tightness at negative pressure of -400 Pa: L1 (M)
  • Tightness at positive pressure of +700 Pa: L1 (M)
  • Filter bypass leakage: F9 at negative and positive pressure
  • Thermal transmittance: T2 (M)
  • Thermal bridging factor: TB3

The cabinets are made of Aluzinc AZ185 class C4 according to EN/ISO 12 944-2 and insulated with 50 mm mineral wool. This results in a low noise level to the surroundings/setup room.

The panel construction minimizes the formation of thermal bridges in the unit.

The motor sections are mounted in vibration dampers, which means less noise and vibration in the ducts, and there is no need to install flexible connections between the unit and the duct system.

The motor sections are retractable for easier service.

The motors are EC type with very high efficiency, meeting the requirements of the EcoDesign directive.

The aggregate is equipped with EXHAUSTO's EXstream impeller, one of the market's leading impellers in terms of low energy consumption and low noise level.

The easily accessible connection box with built-in supply isolator and circuit breakers ensures easy access for connection and adjustment.

The filter panels are easy to replace and can be ordered as filter class Coarse 85% (M5) or ePM1 55% (F7) according to ISO 16890.

VEX100-serien leveres med integreret eftervarmeflade, enten til vand eller el

VEX140 - VEX160:

Montagesokkel med fødder, der kan justeres i højden - 130 - 160 mm.

Montagesoklen er standard for VEX170.

VEX100 IS AVAILABLE AS A SPLIT VERSION.

With some projects, limited space means that internal transport of the air handling unit is difficult or impossible. This is why the VEX100 is available as a split version. It means that the air handling unit can be assembled and tested at the factory as normal – just without sealant. The air handling unit can therefore be easily taken apart at the installation site, transported as single sections, assembled, sealed and commissioned.

The table below shows the dimensions of the largest section (crossflow heat exchanger) and largest cabinet section, so that it can easily be determined whether there is sufficient space to allow internal transport.

Products and accessories references

  • VEX140, horizontal version
    VEX140, horizontal version
  • VEX150, horizontal version
    VEX150, horizontal version
  • VEX160, horizontal version
    VEX160, horizontal version
  • VEX170H
    VEX170H
  • VEX140, in vertical version
    VEX140, in vertical version
  • VEX150, vertical version
    VEX150, vertical version
  • VEX160, vertical version
    VEX160, vertical version

Documents

Showing 1 - y of document
  • VEX140X-150X-160X-170X, EC Declaration of Conformity
    Conformities
    127 KB
  • VEX100 EXact2 Declaration of Conformity
    Conformities
    126 KB
  • VEX100, order form
    Technical & Business documentation
    639 KB
  • VEX140H with HCE electrical heating coil and EXact2, mechanical instruction
    Manuals
    5 MB
  • VEX150H with HCE electrical heating coil and EXact2, mechanical instruction
    Manuals
    5 MB
  • VEX160H with HCE electrical heating coil and EXact2, mechanical instruction
    Manuals
    5 MB
  • VEX170H with HCE electrical heating coil and EXact2, mechanical instruction
    Manuals
    5 MB
  • VEX140V with HCE electrical heating coil and EXact2, mechanical instruction
    Manuals
    5 MB
  • VEX150V with HCE electrical heating coil and EXact2, mechanical instruction
    Manuals
    5 MB
  • VEX160V with HCE electrical heating coil and EXact2, mechanical instruction
    Manuals
    5 MB
  • VEX140H with HCW water heating coil and EXact2, mechanical instruction
    Manuals
    5 MB
  • VEX150H with HCW water heating coil and EXact2, mechanical instruction
    Manuals
    5 MB
  • VEX160H with HCW water heating coil and EXact2, mechanical instruction
    Manuals
    5 MB
  • VEX170H with HCW water heating coil and EXact2, mechanical instruction
    Manuals
    6 MB
  • VEX140V with HCW water heating coil and EXact2, mechanical instruction
    Manuals
    5 MB
  • VEX150V vertical with HCW water heating coil and EXact2, mechanical instruction
    Manuals
    5 MB
  • VEX160V with HCW water heating coil and EXact2, mechanical instruction
    Manuals
    5 MB
  • VEX140H-V-X with HCW water heating coil without controls, , mechanical instruction
    Manuals
    13 MB
  • VEX150H-V-X with HCW water heating coil without controls, , mechanical instruction
    Manuals
    4 MB
  • VEX160H-V with HCW water heating coil without controls, mechanical instruction
    Manuals
    4 MB
  • VEX170H with HCW water heating coil without controls, mechanical instruction
    Manuals
    4 MB
  • VEX140 with HCW water heating coil and EXact2E, electrical instruction
    Manuals
    2 MB
  • VEX150-170 with HCW water heating coil and EXact2, electrical instruction
    Manuals
    4 MB
  • VEX140 with HCW water heating coil without control, electrical instruction
    Manuals
    1 MB
  • VEX150-160 with HCW water heating coil without control, electrical instruction
    Manuals
    1 MB
  • VEX170H with HCW water heating coil without control, electrical instruction
    Manuals
    1 MB
  • VEX140-170 with electrical heating coil HCE and EXact2, electrical instruction
    Manuals
    5 MB
  • EXact2-HMI2 for VEX100/VEX100CF, instruction
    Manuals
    3 MB
  • EXact2-HM2 for VEX100/VEX100CF, menu guide
    Manuals
    632 KB

1 software