EXHAUSTOProductsCooling and heating coilsDX cooling/heating coilDX050x100 DX050x100 DX050x100, dimensioned for VEX270. Merge to pdf Technical data DX050x100 Coil data Number of rows of pipes qty. 3 Number of circuits qty. 18 Face area (H x W) 900 x 1,100 mm Pipe connection DN25 (1") Fin spacing 2.5 mm. Weight (without fluid) 53 kg. Internal volume 9,7 l Merge to pdf Capacity curves DX050x100, output as evaporator and condenser Output as evaporator Conditions: Outdoor temperature 32°C and 40 % RF The diagram shows the air supply temperature at evaporation temperatures of 5, 7 and 9°C, and at various airflow rates (no cold recovery). Output as evaporator Conditions: 5° evaporation/ Δ 5° overheating The diagram shows the air supply temperature after the coil, at outdoor temperatures (air temperature before coil) of 32, 28 and 24°C, at RF of 40 and 55 %, and at various airflow rates (no cold recovery). Output as condenser The diagram shows the air supply temperature after the coil, with air temperatures before the coil (air temperature or heat exchanger) of 0, 5, 10 and 15°C, at condensing temperatures of 40°C and 30°C, and at different airflow rates. Merge to pdf Pressure drop DX050x100, pressure drop across DX coil Add all about the product series DX050x100 Add all about the product
CONTACT US TODAY Get free advice on ventilation products and system solutions Export Requests:EXHAUSTO ExportOdensevej 76DK 5550 Langeskov Tel +45 6566 1234 E-mail: export@exhausto.dk
Calculation programs Use EXHAUSTO's free calculation programs for calculating ventilation plant and system solutions Go to Calculation Programs
VEX Summary Get a quick overview of our entire range of compact VEX air handling units with heat recovery. View the VEX summary here