DX315 large

DX315 large

DX315L is dimensioned for VEX140 and VEX240

Technical data

DX315 large

Coil data
Number of rows of pipes qty. 3
Number of circuits  qty. 6
Face area (H x W) 500 x 500 mm
Pipe connection  DN15 (½")
Fin spacing  2.5 mm.
Weight (without fluid)  21 kg.
Internal volume  2.5 l.

Capacity curves

DX315 large, output as evaporator and condenser

Output as evaporator

Evaporation_curve_DX315L

 

Conditions: Outdoor temperature 32°C and 40 % RF
The diagram shows the air supply temperature at evaporation temperatures of 5, 7 and 9°C, and at various airflow rates (no cold recovery).


Output as evaporator

Evaporation_capacity_DX315L 

Conditions: 5° evaporation/ Δ 5° overheating
The diagram shows the air supply temperature after the coil, at outdoor temperatures (air temperature before coil) of 32, 28 and 24°C, at RF of 40 and 55 %, and at various airflow rates (no cold recovery).


Output as condenser

Condensator_capacity_DX315S

 

The diagram shows the air supply temperature after the coil, with air temperatures before the coil (air temperature or heat exchanger) of 0, 5, 10 and 15°C, at condensing temperatures of 40°C and 30°C, and at different airflow rates.


Pressure drop

DX315 large, pressure drop across DX coil

Pressure_loss_DX315L


Add all about the product series DX315 large

CONTACT US TODAY

Get free advice on ventilation products and system solutions


Export Requests:
EXHAUSTO Export
Odensevej 76
DK 5550 Langeskov

Tel +45 6566 1234
E-mail: export@exhausto.dk

Calculation programs

Use EXHAUSTO's free calculation programs for calculating ventilation plant and system solutions

Go to Calculation Programs
Vex overview

VEX Summary

Get a quick overview of our entire range of compact VEX air handling units with heat recovery.

View the VEX summary here