EXHAUSTOProductsCooling and heating coils HE/HCE electric heating coilHE315 HE315 Electric heating coil with spigot dimension Ø315. For use with VEX320C, VEX330C and VEX330H. Merge to pdf Technical data HE315 for VEX320-330 Data HE31504BUE HE31508BUE Output 3.9 kW 7.8 kW Min. airflow 100 m3/h 100 m3/h Modulating steps 1 step 1 step Weight 20 kg. 20 kg. Merge to pdf Dimensioning VEX with spigot dimension Ø315 and EXact2 control system Size Output (kW) Voltage(V) Power consumption (A) (max. phase current) HE31504BUE 3.9 kW 3 x 400 V + PE ∼ 50 Hz 5,7 HE31508BUE 7.8 kW 3 x 400 V + PE ∼ 50 Hz 11,3 Find wiring diagram for connecting coils and power data VEX320-330C, wiring diagram - coils VEX330H, wiring diagram - coils Merge to pdf Select output HE315: 3.9 or 7.8 kW Merge to pdf Dimensional drawing HE315 for VEX320-330 Add all about the product series HE315 Add all about the product
CONTACT US TODAY Get free advice on ventilation products and system solutions Export Requests:EXHAUSTO ExportOdensevej 76DK 5550 Langeskov Tel +45 6566 1236 E-mail: export@exhausto.dk
Calculation programs Use EXHAUSTO's free calculation programs for calculating ventilation plant and system solutions Go to Calculation Programs
VEX Summary Get a quick overview of our entire range of compact VEX air handling units with heat recovery. View the VEX summary here