HWR

HWR

HWR heat recovery coil in which surplus heat, e.g. from refrigerators, can be used to heat the supply air.

HWR, construction

Function and application

This coil has been specially manufactured for a so-called shop solution, in which surplus heat from refrigerators etc. is recycled. This means that surplus heat from refrigerators can be used to heat up the supply air.

The water is supplied through pipes which exit the unit at the front. The number of pipes and circuits depends on the applicable heating or cooling requirement.

VEX4030HWR
VEX4000 HWR


Construction

HWR coils are made from copper piping with aluminium fins integrated in steel panel frames.


Connection

Pipe connections and panels must be dismounted prior to pulling out.

Design options

Heat recovery coils are available in different versions with several coil combinations.


Technical data for duct-mounted HWR coils

Duct-mounted HWR heat recovery coil

 Data for HWR for VEX4010   HWR1  HWR2
 Test pressure 3000 kPa 3000 kPa
 Max. operating pressure 1600 kPa 1600 kPa
 Connection dimension 2 x Ø28 mm 2 x Ø35 mm
 Fin spacing 1.8 mm 2.5 mm
 Weight (without fluid) 17 kg 15 kg
 Internal volume 6.6 l 6.9 l
Data for HWR for VEX4020   HWR1  HWR2
 Test pressure 3000 kPa 3000 kPa
 Max. operating pressure 1600 kPa 1600 kPa
 Connection dimension 2 x Ø28 mm 2 x Ø35 mm
 Fin spacing 1.8 mm 2.5 mm
 Weight (without fluid) 22 kg 19 kg
 Internal volume 8.2 l 8.5 l
Data for HWR for VEX4030   HWR1  HWR2
 Test pressure 3000 kPa 3000 kPa
 Max. operating pressure 1600 kPa 1600 kPa
 Connection dimension 2 x Ø35 mm 2 x Ø54 mm
 Fin spacing 1.8 mm 2.2 mm
 Weight (without fluid) 34.0 kg 31.0 kg
 Internal volume 13.2 l 14.7 l
Data for HWR for VEX4040   HWR1  HWR2
 Test pressure 3000 kPa 3000 kPa
 Max. operating pressure 1600 kPa 1600 kPa
 Connection dimension 2 x Ø35 mm 2 x Ø54 mm
 Fin spacing 2.0 mm 2.5 mm
 Weight (without fluid) 41.0 kg 32.0 kg
 Internal volume 16.4 l 15.7 l
Data for HWR for VEX4050   HWR1  HWR2
 Test pressure 3000 kPa 3000 kPa
 Max. operating pressure 1600 kPa 1600 kPa
 Connection dimension 2 x Ø35 mm 2 x Ø54 mm
 Fin spacing 1.8 mm 2.5 mm
 Weight (without fluid) 47.0 kg 40.0 kg 
 Internal volume 17.8 l 19.4 l
Data for HWR for VEX4060   HWR1  HWR2
 Test pressure 3000 kPa 3000 kPa
 Max. operating pressure 1600 kPa 1600 kPa
 Connection dimension 2 x Ø54 mm 2 x Ø70 mm
 Fin spacing 1.8 mm 2.5 mm
 Weight (without fluid) 61 kg 52 kg
 Internal volume 24.7 l 27.0 l
 Data for HWR for VEX4070   HWR1  HWR2
 Test pressure 3000 kPa 3000 kPa
 Max. operating pressure 1600 kPa 1600 kPa
 Connection dimension 2 x Ø54 mm 2 x Ø70 mm
 Fin spacing 1.8 mm 2.5 mm
 Weight (without fluid) 68 kg 59 kg
 Internal volume 27.5 l 29.6 l
Data for HWR for VEX4080   HWR1  HWR2
 Test pressure 3000 kPa 3000 kPa
 Max. operating pressure 1600 kPa 1600 kPa
 Connection dimension 2 x Ø54 mm
2 x Ø102 mm
 Fin spacing 1.8 mm 2.5 mm
 Weight (without fluid) 85 kg 85 kg
 Internal volume 33.9 l 43.3 l
Data for HWR for VEX4090   HWR1  HWR2
 Test pressure 3000 kPa 3000 kPa
 Max. operating pressure 1600 kPa 1600 kPa
 Connection dimension 2 x Ø54 mm
2 x Ø102 mm
 Fin spacing 1.8 mm 2.5 mm
 Weight (without fluid) 104 kg 90 kg
 Internal volume 40.9 l 51.4 l
Data for HWR for VEX4100   HWR1  HWR2
 Test pressure 3000 kPa 3000 kPa
 Max. operating pressure 1600 kPa 1600 kPa
 Connection dimension 2 x Ø54 mm
2 x Ø102 mm
 Fin spacing 1.8 mm 2.5 mm
 Weight (without fluid) 136 kg 117 kg
 Internal volume 53.0 l 65.6 l

Technical data for duct-mounted HWRC coils

Built-in heat recovery coils (HWRC)

 Data for HWRC for VEX4010   HWRC1  HWRC2
 Test pressure 3000 kPa 3000 kPa
 Max. operating pressure 1600 kPa 1600 kPa
 Connection dimension 2 x Ø22 mm 2 x Ø35 mm
 Fin spacing 1.8 mm 2.5 mm
 Internal volume 7.4 l 7.7 l
 Data for HWRC for VEX4020   HWRC1  HWRC2
 Test pressure 3000 kPa 3000 kPa
 Max. operating pressure 1600 kPa 1600 kPa
 Connection dimension 2 x Ø28 mm 2 x Ø35 mm
 Fin spacing 1.8 mm 2.5 mm
 Internal volume  9.4 l 9.6 l
 Data for HWRC for VEX4030   HWRC1  HWRC2
 Test pressure 3000 kPa 3000 kPa
 Max. operating pressure 1600 kPa 1600 kPa
 Connection dimension 2 x Ø35 mm 2 x Ø54 mm
 Fin spacing 1.8 mm 2.5 mm
 Internal volume 14.5 l 15.9 l
 Data for HWRC for VEX4040   HWRC1  HWRC2
 Test pressure 3000 kPa 3000 kPa
 Max. operating pressure 1600 kPa 1600 kPa
 Connection dimension 2 x Ø35 mm
2 x Ø54 mm
 Fin spacing 1.8 mm 2.5 mm
 Internal volume 18.3 l 17.9 l
 Data for HWRC for VEX4050   HWRC1  HWRC2
 Test pressure 3000 kPa 3000 kPa
 Max. operating pressure 1600 kPa 1600 kPa
 Connection dimension 2 x Ø35 mm
2 x Ø54 mm
 Fin spacing 1.8 mm 2.5 mm
 Internal volume 18.6 l 20.8 l
 Data for HWRC for VEX4060   HWRC1  HWRC2
 Test pressure 3000 kPa 3000 kPa
 Max. operating pressure 1600 kPa 1600 kPa
 Connection dimension 2 x Ø70 mm 2 x Ø70 mm
 Fin spacing 1.8 mm 2.5 mm
 Internal volume 29.7 l 29.6 l
 Data for HWRC for VEX4070   HWRC1  HWRC2
 Test pressure 3000 kPa 3000 kPa
 Max. operating pressure 1600 kPa 1600 kPa
 Connection dimension 2 x Ø70 mm 2 x Ø70 mm
 Fin spacing 1.8 mm 2.5 mm
 Internal volume 32.3 l 32.3 l
 Data for HWRC for VEX4080   HWRC1  HWRC2
 Test pressure 3000 kPa 3000 kPa
 Max. operating pressure 1600 kPa 1600 kPa
 Connection dimension 2 x Ø54 mm 2 x Ø102 mm
 Fin spacing 1.8 mm 2.5 mm
 Internal volume 35.7 l 46.5 l
 Data for HWRC for VEX4090   HWRC1  HWRC2
 Test pressure 3000 kPa 3000 kPa
 Max. operating pressure 1600 kPa 1600 kPa
 Connection dimension 2 x Ø54 mm 2 x Ø102 mm
 Fin spacing 1.8 mm 2.5 mm
 Internal volume 46.7 l 58.3 l
 Data for HWRC for VEX4100   HWRC1  HWRC2
 Test pressure 3000 kPa 3000 kPa
 Max. operating pressure 1600 kPa 1600 kPa
 Connection dimension 2 x Ø70 mm 2 x Ø102 mm
 Fin spacing 1.8 mm 2.5 mm
 Internal volume 62.1 l  71.7 l
Dimensions, dimensions table for section with a coil

Section with a built-in coil

Dimensions table

VEX4000 model ½ Height/Height  Length   Depth
VEX4010 [mm] 702/1309 480 1055
VEX4020 [mm]
702/1309 480 1275
VEX4030 [mm] 797/1499 480 1549
VEX4040 [mm]
847/1599 480 1630
VEX4050 [mm]
919/1744 480 1755
VEX4060 [mm]
1077/2069 480 1930
VEX4070 [mm]  1077/2069 480 2115
VEX4080 [mm]
1209/2494 480 2325
VEX4090 [mm]
1334/2744 480 2625
VEX4100 [mm]
1474/3024 480 2895

The indicated dimensions are the dimensions for the section - use EXselectPRO to get the correct dimensions for the whole air handling unit, including assembly fittings and seals.


Dimensions, dimensions table for section with two coils

Section with two built-in coils

Dimensions table

VEX4000 model ½ Height/Height  Length   Depth
VEX4010 [mm] 702/1309 1404 1055
VEX4020 [mm]
702/1309 1404 1275
VEX4030 [mm] 797/1499 1404 1549
VEX4040 [mm]
847/1599 1404 1630
VEX4050 [mm]
919/1744 1404 1755
VEX4060 [mm]
1077/2069 1404 1930
VEX4070 [mm]  1077/2069 1404 2115
VEX4080 [mm]
1209/2494 1404 2325
VEX4090 [mm]
1334/2744 1404 2625
VEX4100 [mm]
1474/3024 1404 2895

The indicated dimensions are the dimensions for the section - use EXselectPRO to get the correct dimensions for the whole air handling unit, including assembly fittings and seals.


Add all about the product series HWR

CONTACT US TODAY

Get free advice on ventilation products and system solutions


Export Requests:
EXHAUSTO Export
Odensevej 76
DK 5550 Langeskov

Tel +45 6566 1236
E-mail: export@exhausto.dk

Calculation programs

Use EXHAUSTO's free calculation programs for calculating ventilation plant and system solutions

Go to Calculation Programs
Vex overview

VEX Summary

Get a quick overview of our entire range of compact VEX air handling units with heat recovery.

View the VEX summary here