EXcon Control system

EXcon

Control system

EXcon control system for controlling the indoor climate. Our modular air handling units as well as CX3000 and DEX3000 are equipped with the EXcon control system.
EXcon
EXcon control systems ensure optimum control of the indoor climate in practically every application area. The EXcon control system also offers special solutions for application areas that require specific control facilities, e.g. shop solutions that ensure the correct indoor climate, including areas with humidification, special cooling control and precise temperature control.

EXcon control systems can be used for controlling airflows, heating, cooling, etc. The operating program is configured for how and when the control system will switch between the integral functions. If necessary, the program can be overridden with temporary forced control, after which it will return to the active operating program.

OPERATION OF THE EXCON CONTROL SYSTEM
The EXcon control system can be operated from the remote control, CTS or a web server over a network or via WiFi router. 
EXcon

Product advantages

  • User-friendly
  • Reliable
  • Optimum costs
  • Flexible
  • Future-proof

User-friendly

  • Integral user-friendly web server with information level adaptable to user

Reliable

  • With modular BUS system for safe operation
  • Security from unauthorised access
  • Effective troubleshooting and monitoring

Cost-effective:

  • Simple implementation, training and maintenance
  • Multiple adjustment options
  • Uniquely user-friendly
  • Energy savings through optimum operation

Flexible:

  • A customisable platform
  • Possible upgrade

Future-proof:

  • Software updating via SD card
  • Option to integrate into multiple CTS systems

Integral functions in the control system

  • Night-time reduced duty
  • Alarm log and data log
  • Control using a day, week or year plan
  • Extended operation
  • External forced operation with run-on time
  • Alarm email (requires local mail server)
  • Summer night cooling
  • Outdoor air temperature compensation
  • Automatic summer/winter time changeover
  • Static or dynamic filter monitoring
  • Zone control for four zones (requires zone modules) read more here
  • Portal solution, total monitoring of five systems with Excon or EXact2 control system
    • Via CTS – More than 800 registers or objects available (modbus/bacnet)
  • Digital inputs for:
    • External resetting of alarms
    • External low, medium and high speed
    • External start/stop
  • Digital inputs for:
    • A alarm
    • B alarm (configurable for low/high speed or summer night cooling)
    • Operating relay
    • Fire alarm
    • Alarm reset

Control methods

  • Constant pressure
  • Constant airflow
  • Constant CO2
  • Fan Optimiser
  • Constant motor speed
  • Adaptive pressure control (patented solution for energy optimisation of VAV systems)
  • External 0–10V with supply air/extract air slave
  • ALC (requires accessory)

Temperature regulation

  • Constant supply air temperature
  • Constant extract air temperature
  • Constant room temperature
  • Constant difference between extract air and supply air
  • Summer and winter compensation
  • Recirculated air heating (option)
  • Summer night cooling

Network communication:

  • Network communication supports BACNet via TCP/IP and MODBUS via RS485 or TCP/IP.

Zone Control

  • Zone control makes it possible to control ventilation in up to 4 different VAV/CAV zones directly from the VEX4000 unit using EXcon Master.
  • This is perfect for smaller installations with zones where different rooms have different requirements for the indoor climate
  • Zone control can be used for control of:
    • VAV dampers
    • Cooling and heating valves
    • Humidity
    • VOC/CO2
    • Room temperature cooling

Products and accessories references

Documents

Showing 1 - y of document
  • EXcon SW, LON Protocol user manual
    Manuals
    2 MB
  • EXcon HMI Touch panel for VEX4000 and VEX5000
    Manuals
    1 MB
  • EXcon instruction VEX5000 control
    Manuals
    32 MB
  • EXcon Zone Control Module A (analog)
    Manuals
    5 MB
  • EXcon Zone control Modul M (Modbus)
    Manuals
    4 MB
  • Excon Zone control RPT-20T Touch Room Panel
    Manuals
    2 MB
  • EXcon WAP, Wireless Access Point guide
    Manuals
    295 KB
  • EXcon OJ GreenZone Module MP-Bus, instruction
    Manuals
    2 MB
  • EXcon PTH-6201/PTH6202/PTH6502, instruction
    Manuals
    777 KB
  • EXcon instruction DEX3000 control
    Manuals
    12 MB
  • EXcon SW652 Modbus BACnet protocol
    Manuals
    2 MB
  • Excon, BACnet edi file (.csv)
    Guides
    79 KB
  • EXcon control for VEX4000, operation and configuration
    Manuals
    30 MB
  • EXcon zone control for VEX4000, instruction
    Manuals
    2 MB
  • EXcon for CX3000, DEX3000, VEX4000, VEX5000, VEX300T, alarm list
    Manuals
    635 KB
  • EXcon dehumidifier-KIT, fitting and configuration
    Manuals
    3 MB
  • EXcon control for DEX3000, operation and configuration
    Manuals
    13 MB
  • EXcon control for CX3000, operation and configuration
    Manuals
    16 MB
  • EXcon automatik till VEX4000
    Handböcker
    30 MB