VEX160H-V

VEX160 is available in horizontal and vertical versions

Technical data

Technical data, VEX160H-V

Unit data
Min. airflow
600 m³/h
Max. airflow
4,480 m³/h
Absorbed power 4,8 kW
Power supply 3 x 400 V + N + PE~ 50 Hz
Max. phase current 15,5 A *
Max. neutral current 23.5 A
Weight
Operation-ready unit
- with cross-flow heat exchanger type A
- with  standard cross-flow heat exchanger 

360 kg
355 kg
For transport into the location 202 kg **
Motor and motor control (MC) data
Motor type EC motor
Motor class in accordance with IEC TS 60034-30-2 IE5 (Ultra Premium Efficiency)
Voltage input 1 x 230 V
Current overload protection Built-in
Regulation Variable via motor control (MC)
Control signal With integrated control system:
Modbus
For third-party control system:
0-10 V DC 
* (power consumption is taken from two phases and is not sinusoidal)
** (excl. doors, heat exchanger and fan units)
 

Heating coils

Electric heating coil (HCE) 14.4 kW
Absorbed power total 19.2 kW
Power supply 3 x 400 V + N + PE~ 50 Hz
Max. phase current 36.5 A
Electric heating coil (HCE) 21.6 kW
Absorbed power total 26.4 kW
Power supply 3 x 400 V + N + PE~ 50 Hz
Max. phase current 46.7 A
Electric heating coil (HCE) 28.8 kW
Absorbed power total 33.6 kW
Power supply 3 x 400 V + N + PE~ 50 Hz
Max. phase current 57.0 A
Water heating coil (HCW)

Test pressure
3000 kPa
Max. operating pressure
1000 kPa
Number of rows of pipes
Qty. 2
Number of circuits
Qty. 5
Face area (H x W)
475 x 760 mm
Pipe connection
DN20 (¾")
Fin spacing
2,1 mm
Weight (without fluid)
9,5 kg
Water content
2,4 l

 

Fan data

 
Max. total efficiency (A-D) 57.1%
ECO measurement set-up (A-D) A
Efficiency level requirements 62N (2015)
ECO efficiency level during optimal operating point 67.2N

Motor data (optimal operating point)

EC motor With motor controller
Absorbed power 2.36 kW
Airflow 4551 m3/h
Total pressure 1065 Pa
RPM during optimal operating point 3078

Conditions:
- Density = 1.2 kg/m3
- Pressure ratio < 1.11
- other points in acc. with EC327/2011 (see product instructions)

Temperature efficiency

Temperature efficiency, VEX160H-V

Temperature efficiency, VEX160
stiplet streg
Efficiency with condensation:
Extract air = 20°C/55 RH
Outdoor air  = -10°C/50 RH
Balance between supply air/extract air = 1,0
kort-lang-stiplet-streg
Efficiency without condensation with imbalance:
Extract air = 25°C/28 RH
Outdoor air = 5°C/50 RH
Balance between supply air/extract air  = 0,8
fed streg Efficiency without condensation in acc. with EN308:
Extract air = 25°C/28 RH
Outdoor air = 5°C/50 RH
Balance between supply air/extract air = 1,0

Calculation

The temperature efficiency of the VEX air handling units are shown at different airflow ratios, calculated as:


t2,1 = Temperature of outdoor air (fresh air)
t2,2 = Temperature of supply air
t1,1 = Temperature of extract air
Extract air = 25 ºC / 30 % RH
Outdoor air (fresh air) = 5 ºC / 50 % RH
Temperature efficiency is stated in accordance with EN308 for dry heat recovery and is increased by condensation.
Dimensional drawings, Horizontal

Dimensional drawings, VEX160H

VEX160H - Horizontal, Left (unit dimensions in mm)

RD10272 VEX160HL HCW målskitse

 

 desired spigot location, position A or B, to be specified in order.
*) Allow a height for service in front of the unit equivalent to the unit width.
**) Allow a min. of 300 mm free height for service.

 

VEX160H - Horizontal,Right (unit dimensions in mm)

RD10273 VEX160HR HCW målskitse

 

1.1 Extract air 1.2 Exhaust air 2.1 Outdoor air 2.2 Supply air

 desired spigot location, position A or B, to be specified in order.
*) Allow a height for service in front of the unit equivalent to the unit width.
**) Allow a min. of 300 mm free height for service.

Dimensional drawings, Vertical

Dimensional drawings, VEX160V

VEX160V - Vertical, Left (unit dimensions in mm)

RD10315 VEX160VL HCW målskitse

 

 desired spigot location, position A or B, to be specified in order.
*) Allow a height for service in front of the unit equivalent to the unit width.
**) Allow a min. of 300 mm free height for service.

 

VEX160V - Vertical, Right (unit dimensions in mm)

RD10317 VEX160VR HCW målskitse

 

1.1 Extract air 1.2 Exhaust air 2.1 Outdoor air 2.2 Supply air

 desired spigot location, position A or B, to be specified in order.
*) Allow a height for service in front of the unit equivalent to the unit width.
**) Allow a min. of 300 mm free height for service.

Cooling and heating coils

Cooling and heating coils, VEX160CF

The following cooling and heating coils are suitable for VEX160/VEX160CF

Type Model
CW cooling coil (water)  CW500I
CW065x100U
DX cooling/heating coil DX500

Add all about the product series VEX160H-V

CONTACT US TODAY

Get free advice on ventilation products and system solutions


Export Requests:
EXHAUSTO Export
Odensevej 76
DK 5550 Langeskov

Tel +45 6566 1236
E-mail: export@exhausto.dk

Calculation programs

Use EXHAUSTO's free calculation programs for calculating ventilation plant and system solutions

Go to Calculation Programs
Vex overview

VEX Summary

Get a quick overview of our entire range of compact VEX air handling units with heat recovery.

View the VEX summary here