VEX40T Technical data
VEX40T Sound data
An extremely quiet air handling unit
Sound/pressure/level Lp(A)
|
|
VEX40T Premium |
VEX40T Classic |
Air volume |
Pressure |
Not build in |
Build into cupboard |
Not build in |
Build into cupboard |
[m3/h] |
[Pa] |
[dB(A)] |
[dB(A)] |
[dB(A)] |
[dB(A)] |
86 |
80 |
32 |
30 |
33 |
31 |
86 |
100 |
35 |
32 |
35 |
33 |
126 |
100 |
35 |
30 |
38 |
33 |
162 |
100 |
37 |
32 |
39 |
34 |
224 |
100 |
39 |
34 |
43 |
38 |
The sound pressure level at room sound attenuation 20m2-Sabin in a one meter distance and VEX40T mounted in kitchen-, ardrobe with closed door or visible in the middel of a wall
Sound pressure level Lw(A) - connections = supply air and exhaust air
Air volume
|
Pressure
|
Frequency split up Sound output
|
Total
|
[m3/h] |
[Pa] |
[dB(A) (1 pW)] |
[dB(A)] |
86 |
80 |
25 |
34 |
40 |
39 |
30 |
26 |
16 |
43 |
86 |
100 |
29 |
37 |
42 |
41 |
33 |
30 |
20 |
46 |
126 |
100 |
28 |
37 |
43 |
44 |
35 |
31 |
22 |
47 |
162 |
100 |
28 |
39 |
45 |
47 |
38 |
35 |
27 |
50 |
224 |
100 |
34 |
44 |
50 |
51 |
43 |
42 |
36 |
55 |
Sound pressure level Lw(A) - connections = extract air and outdoor air
Air volume |
Pressure |
Frequency split up Sound output |
Total |
[m3/h] |
[Pa] |
[dB(A) (1 pW)] |
[dB(A)] |
|
|
125 Hz |
250 Hz |
500 Hz |
1000 Hz |
2000 Hz |
4000 Hz* |
8000 Hz* |
|
86 |
80 |
4 |
11 |
16 |
10 |
2 |
- |
- |
18 |
86 |
100 |
6 |
11 |
17 |
12 |
4 |
- |
- |
19 |
126 |
100 |
6 |
14 |
18 |
13 |
5 |
- |
- |
21 |
162 |
100 |
6 |
17 |
19 |
16 |
7 |
- |
- |
23 |
224 |
100 |
10 |
20 |
22 |
18 |
10 |
- |
- |
26 |
*= the value is lower than the referencevalue (1pW)