Construction
The coils are made from copper piping with aluminium fins integrated in steel panel frames. The number of pipes and circuits depends on the applicable heating or cooling requirement.
In the units, the coils are mounted on guide rails for pulling out, inspection and maintenance. Pipe connections and panels must be dismounted prior to pulling out.
The cooling function is constructed with a corrosion-resistant base tray under the cooling coil, and contains space for the droplet separator, which should be installed in the case of water cooling and air speeds greater than 2.5 m/s.
The base tray is designed with a fall to the drain, in order to avoid accumulating stagnant water. The drains have smooth piping and exit the panel on the operating side, where a water trap must be fitted.
Connections - generally for all coils
It is important to ensure correct flow through the coils. For this reason, the coils should/must be dimensioned for the actual circumstances, such as airflow, temperature settings for the water in the coil and the desired delivery temperature of the coil.