VEX330H1

Technical data

Technical data, VEX330H1

Unit data:

Min. airflow 70 m³/h
Max. airflow 900 m³/h
Power consumption 0.6 kW
Power supply 1 x 230 V + N + PE ∼ 50 Hz
Max. phase current 3.1 A
Operational-ready unit weight 153 kg (without a removable panel = 143 kg)
Fluid temperature (air) -40°C to +40°C
Ambient temperature (operating) -30°C to +50°C

 

At temperatures below -25˚C (with outdoor installation), use of a thermostatically controlled heater in automated control box is recommended.

 

Fan data

 
Max. total efficiency (A-D) 60.1 %
ECO measurement set-up (A-D) A
Efficiency level requirements 62N (2015)
ECO efficiency level during optimal operating point 78.7N

 

Motor data (optimal operating point)

EC motor With motor controller
Power consumption 0.17 kW
Airflow 1,005 m3/h
Total pressure 322 Pa
RPM during optimal operating point 2,555 

 

 Conditions:

- Density = 1.2 kg/m3
- Pressure ratio < 1,11
- other points in acc. with EC327/2011 (see product instructions)

Temperature efficiency

Temperature efficiency, VEX330H1

The temperature efficiency and, to a lesser extent, the SFP/SEL values for a specific air handling unit are closely connected to the heat exchanger itself and depend upon the manufacturer. As suppliers can change from time to time, small changes in the technical data can occur, which is why it is always recommended that you perform a calculation for the particular project using our calculation software, EXselectPRO.

VEX330H temperaturvirkningsgrad
The curve is intended as a guideline, and it is recommended that a calculation be performed using the calculation software EXselectPRO for the individual project.

stiplet streg
Efficiency with condensation:
Extract air = 20°C/55 RH
Outdoor air  = -10°C/50 RH
Balance between supply air/extract air = 1,0
kort-lang-stiplet-streg
Efficiency without condensation with imbalance:
Extract air = 25°C/28 RH
Outdoor air = 5°C/50 RH
Balance between supply air/extract air  = 0,8
fed streg Efficiency without condensation in acc. with EN308:
Extract air = 25°C/28 RH
Outdoor air = 5°C/50 RH
Balance between supply air/extract air = 1,0

 

 

Calculation

The temperature efficiency of the VEX units is shown at different airflow ratios, calculated as:


t2,1 = Temperature of outdoor air (fresh air)
t2,2 = Temperature of supply air
t1,1 = Temperature of extract air
Dimensional drawings

Dimensional drawings, VEX330H1 

 

 

 

VEX330H1 OD - for outdoor installation with base (accessory)

 VEX330H OD målskitse

VEX330H accessories, heating coils

Position

VEX330H målskema for varmeflader



Cooling and heating coils

Cooling and heating coils, VEX320-330

The following cooling and heating coils are suitable for VEX320-330

Type Model
HE electric heating coil  HE315 - 2 sizes 3.9 kW and 7.8 kW
HW water heating coil  HW315S
HW315M
HW315L
DX cooling/heating coil

DX315S (for VEX320 and VEX330C1/330H1)
DX315M (for VEX330C2/330H2)

Add all about the product series VEX330H1

CONTACT US TODAY

Get free advice on ventilation products and system solutions


Export Requests:
EXHAUSTO Export
Odensevej 76
DK 5550 Langeskov

Tel +45 6566 1234
E-mail: export@exhausto.dk

Calculation programs

Use EXHAUSTO's free calculation programs for calculating ventilation plant and system solutions

Go to Calculation Programs
Vex overview

VEX Summary

Get a quick overview of our entire range of compact VEX air handling units with heat recovery.

View the VEX summary here