VEX350/360/370 Control system accessories

MIO2 module

MIO2 - Modbus communication module


MIO2-module


Is used for connection the CO2- moisture- and motion sensor for example, or the TIMERBUTTON for the EXact2 control. 



How many sensors can be connected per MIO2-module?

The sensors emit a 0 -10 V signal (CO2- or moisture sensor for example):
1 sensor per MIO2-module

Sensors which emit an ON/OFF signal (such as a PIR sensor or TIMERBUTTON):
4 Sensors in parallel connection per MIO2-module.

Connect to VEX via modbus.

MIO2 (Modbus input, output)
Analogue input 0-10 V DC
Analogue output 0-10 V DC
Digital input 24 V DC
Digital output open collector 1 A
Relay output 250 V max. 8 A, AC1
Temperature in NTC 10 kΩ @ 25 °C
PIR sensors

PIR Control system accessories

For direct override


MIO-PIR

Motion sensor including Modbus communication module (MIO-module).

Overrides the air handling unit if there is movement in premises where it is installed. 4 PIR sensors can be connected for each MIO-module.

Cut-out delay 10 min.



PIRB-AS

Motion sensor with Modbus communication, which can be connected directly to the external bus of the air handling unit, without the use of an MIO-module.

Overrides the air handling unit if there is movement in premises where it is installed.

Cut-out delay Adjustable 10/30/60/120 min.


For individual zone control


PIR

Motion sensor can be connected to an M-module, or be used for autonomous control of ventilation.

Digital ON/OFF signal.


PIR-sensor
Length, height, width 66 mm x 44 mm x 66 mm
Detection area Angle of coverage: 100°, Reach: ca. 5 m
Output Relay: 2A/30V DC
Weight 56 grammes
Temperature range 0 - 40°C
Supply voltage 24VAC (18 - 26V DC)
Power consumption Type: 500mW, Max: 1W
IP 20
CO2 sensor

CO2 Control system accessories

For direct override


MIO-CO2-DUCT

CO2 DUCT

CO2sensor for duct mounting including Modbus communication module (MIO-module).

Overrides the unit in case of CO2 overload. 



MIO CO2 ROOM

CO2sensor for room mounting including Modbus communication module (MIO-module).

Overrides the unit in case of CO2overload.

Can be re-programmed and comes with different limit values, also with regards to combined CO2 and temperature control. (at extra cost)


CO2-DUCT/CO2-ROOM
Supply 24V AC/DC
Control signal, analogue output 0-10 V DC
Measuring range 0-2000 ppm
Accuracy +/- 20 ppm @ 25 °C

 

For individual zone control


CO2-DUCT

CO2 DUCT

CO2-sensor for duct mounting, for control of dampers by autonomous control of the ventilation.

Analogue 0 - 10 V (0 - 2000 ppm)

Can be re-programmed and supplied with different limit values. Specified when ordering (at extra cost) 


 

CO2 ROOM

CO2-sensor for room mounting, for control of dampers by autonomous control of the ventilation.

Analogue 0 - 10 V (0 - 2000 ppm)
IP: 30

Can be re-programmed and supplied with different limit values, also with combined CO2 and temperature control. Specified when ordering (at extra cost)


KCO2

KCO2

CO2-sensor for duct mounting,for control of dampers by autonomous control of the ventilation.

Analogue 0 - 10 V (0 - 2000 ppm)
IP: 65


KCO21000

KCO2

CO2-sensor for duct mounting,for control of dampers by autonomous control of the ventilation.

Analogue 0 - 10 V (0 - 1000 ppm)
IP: 65


RCO2

RCO2

CO2-sensor for room mounting, for control of dampers by autonomous control of the ventilation.

Analogue 0 - 10 V (0 - 2000 ppm)
IP: 30


RCO21000

RCO2

CO2-sensor for room mounting, for control of dampers by autonomous control of the ventilation.

Analogue 0 - 10 V (0 - 1000 ppm)
IP: 30


 KCO2/RCO2/KCO21000/RCO21000
Supply 24V AC/DC
Controlsignal, analogue output 0-10VDC
Accuracy +/- 100 ppm
RH sensors

RH humidity sensors

For direct override


MIO-RH-ROOM

RCO2

Humidity sensor  for room incl. Modbus communication module (MIO module).

Overrides the unit with humidity  load.



For independent zone control


RFF

RFF

Humidity sensor for room fitting for autonomous control of ventilation.

IP: 30

RFF
Power supply 24 VAC, 15–36 VDC
Control signal, analogue output 0–10 VDC
Measurement range 0–100% RH
Tolerance +/- 3% @ 20°C

TS sensor

TS Temperature sensors

For direct override


MIO-TS-DUCT

TS-DUCT

Temperature sensor for room mounting incl. Modbus communication module (MIO-module).

Oversteers air handling unit by temperature changes.


MIO-TS-ROOM

TS ROOM

Temperature sensor for room mounting including Modbus communication module (MIO-module).

Oversteers air handling unit by temperature changes.



TS ROOME / TS DUCTE
Sensor NTC 10 kΩ @ 25 °C
RLQ sensor

RLQ-air quality sensor

For individual zone control


RLQ

RLQ

Air quality sensor for room mounting and autonomous control of ventilation.

IP: 30


 RLQ
Supply 24V AC/DC
Control signal, analogue output 0 - 10V DC
Measuring range 0 - 100% VOC
Accuracy +/- 20%

VOC = Volatile organic compounds

TIMERBUTTON

TIMERBUTTON control system accessory

For direct override.


TIMERBUTTON / TIMERBUTTONEU

TIMERBUTTON

Manual override for comfort ventilation ex. MIO-module.

Can be set for 4 different time intervals:
- 30 min
- 60 min
- 120 min
- 240 min 

Digital ON/OFF


TIMERBUTTON
Operation range, temperature 5 - 40°C
Moisture 5 - 70% RH
Relay output Max. 48V/5A
Colour White
Supply voltage 24V AC/DC
Power consumption Max. 20mA
IP 20 

 

Dimensional sketches

TIMERBUTTON

TIMERBUTTONEU

Pressure control

MPT-DUCT control system accessory

For direct override


MPT DUCT

MPT-DUCT

Pressure sensor for constant pressure regulation with Modbus communication. Can be connected directly to the external bus of the air handling unit, without the use of an MIO-module.

For constant pressure regulation of both the supply air and the extract air ducts, 2 MPT-DUCT are required.

If VAV is used on a duct string, MPTDUCT must be used.


 MPT-DUCT
Supply via Modbus 24V DC
Measuring range 0 - 1250 Pa
Adjustable area in control unit 0 - 1000 Pa
IP 54
HMI2-350-TOUCH control panel

HMI2-350-TOUCH

Control panel for control of the air handling unit


HMI

HMI-for-EXact2-automatik
For operating VEX units with EXact2 control system – with touch display and small help texts explaining the functions under the individual menus


Technical data, HMI2-350-TOUCH

Dimensions H x W x D 99 x 73 x 21/22
Surrounding temperature -20°C - 60°C
Protection class IP20
Communication Modbus RTU

Add all about the product series VEX350/360/370 Control system accessories

CONTACT US TODAY

Get free advice on ventilation products and system solutions


Export Requests:
EXHAUSTO Export
Odensevej 76
DK 5550 Langeskov

Tel +45 6566 1234
E-mail: export@exhausto.dk

Calculation programs

Use EXHAUSTO's free calculation programs for calculating ventilation plant and system solutions

Go to Calculation Programs
Vex overview

VEX Summary

Get a quick overview of our entire range of compact VEX air handling units with heat recovery.

View the VEX summary here