CX3010

Technical data

CX3010 TECHNICAL DATA

Unit data:
Min. airflow at 200 Pa 55 m³/h
Max. airflow at 200 Pa
520 m³/h
Absorbed power 452 W
Power supply 1x230 V + N + PE 50 Hz
Max. phase current

3.4 A

Operational-ready unit weight 125 kg
Fluid temperature (air) -20°C ....+35°C
Temperature, surroundings (operation) -25°C ....+50°C
Temperature, surroundings (transport and storage)

-40°C ....+60°C
Filter selection:

ePM10 50% (M5)
ePM1 50% (F7)
ePM1 80% (F9) (duct-mounted filter box)

Standard filters:
Filter, supply air 
Filter, extract air

 

ePM1 50% (F7)
ePM10 50% (M5)

Cabinet data:

Corrosion class
Insulation class:
Cold bridge class
Density at 700 Pa overpressure:
Density at -400 Pa negative pressure: 



C4
T3 (M)
TB3 (M)
L2
L2

ECO Design Directive data:

Fan data

 
Max. total efficiency (A-D) 56.9
ECO measurement set-up (A-D) A
Efficiency requirements 62N (2015)
ECO efficiency level during optimal operating point 77.6N
 

Motor data (optimal operating point)

EC motor With motor controller (VSD)
Absorbed power 0.15 kW
Airflow 560 m³/h
Total pressure 512 Pa
RPM during optimal operating point 4,710

Requirements:
- Density = 1.2 kg/m³
- Pressure ratio < 1.11
- Other points in acc. with EC327/2011 (see product instructions)


Dimensional drawings

CX3010, dimensional drawings 

Dimensional drawings, CX3010 Left (measurements in mm) 

CX3010L-Dimensions 

Dimensionsal drawings, CX3010 Right (dimensions in mm) 

CX3010R-Dimensions

Temperature efficiency

Temperature efficiency, CX3010

The temperature efficiency and, to a lesser extent, the SFP/SEL values for a specific air handling unit are closely connected to the heat exchanger itself and depend upon the manufacturer. As suppliers can change from time to time, small changes in the technical data can occur, which is why it is always recommended that you perform a calculation for the particular project using our EXselectPRO calculation software.

CX3010-Temperature efficiency
The curve is intended as a guideline, and it is recommended that a calculation be performed using the calculation software EXselectPRO for the individual project

dashed line

Efficiency with condensation:
Extract air = 20 °C/55 % RH
Outdoor air = -10 °C/50 % RH
Balance between supply air/extract air = 1.0

short-long-broken-line

Efficiency without condensation with imbalance:
Extract air = 25 °C/30 % RH
Outdoor air = 5 °C/50 % RH
Balance between supply air/extract air = 0.8
bold line
Efficiency without condensation in acc. with EN308:
Extract air = 25 °C/30 % RH
Outdoor air = 5 °C/50 % RH
Balance between supply air/extract air = 1.0

Calculation 

The temperature efficiency of the CX air handling units are shown at different airflow ratios, calculated as:
formula-supply-air-Extract-air
Formula-temperature-efficiency
t2.1 = Temperature of outdoor air (fresh air)
t2.2 = Temperature of supply air
t1.1 = Temperature of extract air
Sound data

Sound data, CX3010

SOUND EFFECT LEVEL
at airflow 520 m³/h and 200 Pa external pressure

LWA
[dB(A)]

To duct, outdoor air  60
To duct, supply air 79
To duct, extract air 60
To duct, exhaust air 79
For surroundings 48

* For precise sound data, please refer to our EXselectPRO product selection software.

 

 

Technical data for cooling and heating coils

Technical data for cooling and heating coils for CX3010

Integral water heating coil (HW)

Data 
Power rating 2.89 kW
Number of pipe rows  qty. 2
Number of circuits  qty. 1
Face area (H x W)  620 x 95 mm
Connection dimension  DN15 (½")
Fin spacing  2.8 mm
Weight (without fluid) 5.0 kg
Water content 0.5 l

Duct-mounted preheating coil (PHE)

Data
Power rating 3.0 kW 
Minimum airflow 305 m³/h
Steps  1 step
Controller ON/OFF
Weight  27 kg

Duct-mounted heating coil (AHE)

Data
Power rating 3.0 kW 
Minimum airflow     305 m³/h
Steps  1 step
Controller 0-10 V
Weight  28 kg

Integrated cooling/heating coil (CCW)

Data 
Power rating 1.48 kW
Number of pipe rows  3 items
Number of circuits  qty. 1
Face area (H x W)  200 x 254 mm
Connection dimension  DN15 (½")
Fin spacing  2.5 mm
Weight (without fluid) 5.6 kg
Water content 0.9 l

Add all about the product series CX3010

CONTACT US TODAY

Get free advice on ventilation products and system solutions


Export Requests:
EXHAUSTO Export
Odensevej 76
DK 5550 Langeskov

Tel +45 6566 1236
E-mail: export@exhausto.dk

Calculation programs

Use EXHAUSTO's free calculation programs for calculating ventilation plant and system solutions

Go to Calculation Programs
Vex overview

VEX Summary

Get a quick overview of our entire range of compact VEX air handling units with heat recovery.

View the VEX summary here